Environmental Sensors for E-2D/5D/16D>Gas Detection Sensors
Data Sheet
Installation Manual
CAD Drawing
Product Code: E-CMD
Carbon Monoxide Detector, CO
- Continuous air monitoring.
- Pre-set alarm points alert at:
- 70 ppm after 60 to 240 minutes
- 150 ppm after 10 to 50 minutes
- 400 ppm after 4 to 15 minutes
- Flush or surface mount.
- Test functionality of electrochemical CO sensing cell.
- Connect to RJ45 or digital input sensor ports.
- Screw terminal
- To connect to the RJ45 inputs use CAT5/5e/6 cable terminated at one end with RJ45 connector. Connect the un-terminated end to the sensor screw terminal.
- Maximum cable length: 1000 ft (305m)
- LED indicators for operation status and system test.
- Current consumption: 40mA @ 12VDC.
- Powered by E-2D/5D/16D.
- Regulatory approvals: UL
Ordering Information
Part No.
E-CMD
Description
Carbon Monoxide Detector, CO
Data Sheet
Installation Manual
CAD Drawing
Product Code: E-GD-MBP
Gas Detector — Methane, Butane, Propane
- Use to detect leaks of combustible gas (methane, propane, butane, acetylene, etc.)
- Choose between two levels of detection:
- First level:
- Detects methane at concentrations in excess of 0.5%.
- Detects propane/iso-butane at concentrations in excess of 0.3%.
- Second level:
- Detects methane at concentrations in excess of 0.8%.
- Detects propane/iso-butane at concentrations in excess of 0.5%.
- First level:
- Continuous air monitoring.
- Audible alarm signal: 94 dB at 1 foot.
- Relay specifications: level selectable, normally open or normally closed, 250V AC, max 5A.
- Maximum cable length: 1000 ft (305m)
- Powered by E-2D/5D/16D.
- Current consumption: 150mA @ 12VDC.
- Regulatory approvals: CE
Ordering Information
Part No.
E-GD-MBP
Description
Gas Detector — Methane, Butane, Propane
Data Sheet
Installation Manual
CAD Drawing
Product Code: E-H2
Hydrogen Gas Detector
- Use to detect leaks of hydrogen gas in battery monitoring/charging rooms, substations, uninterruptible power supplies (UPS), and hydrogen fueled back-up power systems.
- Alarm set point: 10% LEL hydrogen gas.
- SPDT Alarm and normally-closed output relay.
- Self-restoring or latching options.
- Sensor requires no maintenance or recalibration.
- Includes mounting hardware.
- Voltage supply: 12 to 24 VDC or VAC.
- Can be powered by the E-2D/5D/16D at 12VDC.
- Current consumption: 70mA @ 12VDC.
- Operating temperature: 32 to 120°F (0 to 49°C).
- Dimensions WxDxH (in): 4.5x5x1.63 (114x127x41 mm).
- Powered by E-2D/5D/16D.
Ordering Information
Part No.
E-H2
Description
Hydrogen Gas Detector
Data Sheet
Installation Manual
CAD Drawing
Product Code: E-H2S
Hydrogen Sulfide Detector
- Use to monitor the presence of Hydrogen Sulfide from failed UPS (uninterrupted power supply) lead acid batteries, in paper mills, refineries, waste disposable facilities, etc.
- Measures H2S in a range of 0 to 50 ppm.
- 5A SPDT fan relay controls exhaust fans, valves, or louvers.
- Alerts are based solely on the measured H2S levels reported by the E-H2S.
- Mounts on a 4×4″ electric box.
- Dimensions WxDxH (in): 4.5x4x2.13 (114x102x54 mm).
- Operating temperature: 0 to 125°F (-18 to 52°C).
- Operating and storage relative humidity: 10 to 90% non-condensing RH.
- Power consumption: 3W.
- Requires the E-S420MA-24V to operate.
- Maximum cable length: 500 ft (152 m).
- Powered by E-2D/5D/16D.
- Compatible with the E-2D/5D/16D.
- Regulatory approvals: ETL, UL.
Ordering Information
Part No.
E-H2S
E-S420MA-24V
Description
Hydrogen Sulfide Detector
4-20mA Sensor Converter
Featured Products: ENVIROMUX

ENVIROMUX-2D (Small Enterprise Environment Monitoring System)

ENVIROMUX-5D (Medium Enterprise Environment Monitoring System)

ENVIROMUX-16DEL (Large Enterprise Environment Monitoring System)

ENVIROMUX-MICRO (Micro Environment Monitoring System)

ENVIROMUX-MINI (Mini Environment Monitoring System)