Environmental Sensors for E-2D/5D/16D>Air Flow/Velocity Sensors
Data Sheet
Installation Manual
CAD Drawing
Product Code: E-AFM
Air Flow Sensor
- Reliable mechanical solution for monitoring air flow.
- Reacts to any condition causing insufficient flow of air such as malfunctioning cooling fan, increased friction, or physical blockage.
- Ideal for direct monitoring of a cooling fan, HVAC duct, or under a raised floor.
- Switch contact is closed when air flow is >8.2 ft/s.
- Connection: 2x single strand AWG26, length 18 in.
- Maximum cable length: 1000 ft (305m)
- Regulatory approvals: RoHS
Ordering Information
Part No.
E-AFM
Description
Air Flow Sensor
Data Sheet
Installation Manual
CAD Drawing
Product Code: E-AV-LC-7
Low-Cost Air Velocity Sensor
- Reliable sensor for measurement of air velocity.
- Flow range: 0 to 82 ft/s (0 to 25 m/s).
- Accuracy: ±1.6 ft/s (±0.5 m/s) from 0 to 49 ft/s (0 to 15 m/s) at 70°F (21°C).
- To avoid damaging the E-AV-LC sensor, it should only be operated where it will sense at least some air flow (≥ 8.2 ft/s (2.5 m/s)) daily.
- Includes mounting hardware.
- Operating temperature: 32 to 158°F (0 to 70°C).
- Probe dimensions: 6.3×0.6 inches (160×15 mm).
- Probe material: PA 2200 plastic.
- Length: 7 feet.
- Includes an RJ45 coupler to extend the sensor up to 1,000 feet using CATx cable (minimum 24AWG).
- MTBF: 1,387,280 hours.
- Current consumption: 15mA @ 5VDC, 60mA @ 12VDC.
- Powered by E-2D/5D/16D.
- Compatible with E-2D/5D/16D.
- E-2D: only compatible with Rev C units (features two power inputs).
- Regulatory approvals: CE, RoHS.
- Compatible with E-FSC Fiber Converter/Extender.
- Use to extend sensor up to 1.2 miles (2 km) from the ENVIROMUX unit.
Ordering Information
Part No.
E-AV-LC-7
Description
Length: 7 ft
Data Sheet
Installation Manual
CAD Drawing
Product Code: E-AV-K
Air Velocity Sensor
- Reliable sensor for measurement of air velocity.
- Requires the E-S5VDC sensor converter to operate.
- Maximum cable length: 1000 ft (305m)
- Powered by E-2D/5D/16D.
- Flow range: 0-2000 ft/min (0-10 m/s).
- Accuracy: ±60 ft/min (0.3 m/s) + 4% of measured value.
- Dust resistant design.
- Includes mounting hardware.
- Operating temperature: -4 to 140°F (-20 to 60°C).
- Storage temperature: -22 to 140°F (-30 to 60°C).
- Operating and storage relative humidity: 5 to 95% non-condensing RH.
- Regulatory approvals: CE, RoHS.
- TAA compliant
- Compatible with E-FSC Fiber Converter/Extender.
- Use to extend sensor up to 1.2 miles (2 km) from the ENVIROMUX unit.
Ordering Information
Part No.
E-AV-K
E-S5VDC
Description
Air Velocity Sensor
5VDC Sensor Converter. Required to connect E-AV to E-xD
Featured Products: ENVIROMUX

ENVIROMUX-2D (Small Enterprise Environment Monitoring System)

ENVIROMUX-5D (Medium Enterprise Environment Monitoring System)

ENVIROMUX-16DEL (Large Enterprise Environment Monitoring System)

ENVIROMUX-MICRO (Micro Environment Monitoring System)

ENVIROMUX-MINI (Mini Environment Monitoring System)